TH0530
• Available in 1 kA and 2 kA current specifications
• Measurement frequency: DC ~ 1 kHz
• Accuracy class: 0.005 / class 0.01
• Through-core and direct-in measurement
• The aperture of Ф 70 mm facilitates penetration of high-current wires
• Analog I/V output mode is supported
Power supply |
AC:85 V ~ 265 V / 47 Hz ~ 63 Hz DC:120 V ~ 370 V |
Maximum power consumption |
100 VA |
Warm-up time |
30 minutes |
Working environment |
Temperature: 0°C ~ 50°C Humidity: 30% R·H ~ 80%R·H, no condensation. Others: No electromagnetic field interference. |
Storage environment |
Temperature: -30°C ~ 70°C Humidity: 10% R· H ~ 90%R·H, no condensation. |
Altitude |
0 m ~ 3000 m |
Communication interface |
RS 232 × 1 |
Size |
175 mm (W) × 330 mm
(D) × 275 mm (H) |
Display screen |
5.6-inch color LCD display |
Quality |
Approx 13 kg |
AC direct current measurement
Measurement manner |
Current range |
Resolution |
Frequency Hz |
Measurement uncertainty (k=2) (23°C ± 5°C) |
Temperature coefficient (/°C). (0°C~50°C) |
|||
TH0530 -1 kA |
TH0530 -2 kA |
Class 0.005 |
Class 0.01 |
Class 0.005 |
Class 0.01 |
|||
(ppm*RD+ppm*RG)[1] |
||||||||
Straight-in |
2.5 A |
5 A |
1 μA |
DC |
40 + 10 |
80 + 20 |
3 + 2 |
6 + 4 |
40≤F≤400 |
150 + 50 |
220 + 80 |
||||||
400<F≤1k |
350 + 150 |
350 + 150 |
||||||
10 A |
20 A |
10 μA |
DC |
40 + 10 |
80 + 20 |
3 + 2 |
6 + 4 |
|
40≤F≤400 |
150 + 50 |
220 + 80 |
||||||
400<F≤1k |
350 + 150 |
350 + 150 |
||||||
Piercing |
250 A |
500 A |
100 μA |
DC |
40 + 10 |
80 + 20 |
3 + 2 |
6 + 4 |
40≤F≤400 |
150 + 50 |
220 + 80 |
||||||
400<F≤1k |
350 + 150 |
350 + 150 |
||||||
1 kA |
2 kA |
1 mA |
DC |
40 + 10 |
80 + 20 |
3 + 2 |
6 + 4 |
|
40≤F≤400 |
150 + 50 |
220 + 80 |
||||||
400<F≤1k |
350 + 150 |
350 + 150 |
||||||
Note
[1]: RD is the
reading value and RG is the
range value. |
• Measurement
up to 110%* measuring range
• Measurement
frequency: DC ~ 1 kHz
• Range
switching: manual/automatic gear shifting
• Display
digits: 7 digits, decimal
• Formation of AC and DC current measurement system
• DC stable power supply test
• Battery charge and discharge test and calibration
• Calibrate the multifunction calibrator
• Calibrate the AC and DC current source/meter
• Clamp meter calibration device traceability
• Voltage output reference
• Ripple and distortion measurement