TD3250 Portable Three-phase Energy Meter Tester


• Accuracy: Class 0.02 or 0.05.

• 3PH voltage measurement: 0~480 V.

• 3PH current measurement (direct) : 50 mA~ 12 A.

• 3PH current measurement (clamp) : 100 mA~ 120 A.

• Support electric energy pulse optical/electrical pulse input.

• LCD touch screen.

• Support AC 100 V~264 V wide range supply.

• Support large capacity lithium battery.

• Internal memory, and quickly record test data.

• USB and RS232 interfaces.

TD3250 is a portable standard meter specially used for three-phase energy meter on-site calibration, AC sampling etc. It integrates the functions of electrical parameter measurement, electric energy meter calibration, connection mode identification, harmonic analysis, waveform display, phasor diagram display, data management.

1 Three phase voltage/current measurement

Type

Measurement Mode

Range

Resolution

Accuracy

± (ppm of reading + ppm of range) [1]

Class 0.05

Class 0.02

ACV

Direct Measurement

110 V

1 mV

300 + 200

120 + 80

220 V

1 mV

300 + 200

120 + 80

440 V

1 mV

300 + 200

120 + 80

ACI

Direct Measurement

1 A

10 μA

300 + 200

120 + 80

10 A

100 μA

300 + 200

120 + 80

Clamp Measurement

1 A[2]

10 μA

0.2%*RG

0.1%*RG

5 A

10 μA

0.2%*RG

0.1%*RG

10 A[2]

100 μA

0.2%*RG

0.1%*RG

20 A[2]

100 μA

0.2%*RG

0.1%*RG

100 A[2]

1 mA

< 50 A: 0.2%*RG

≥ 50 A: 0.5%*RG

< 50 A: 0.1%*RG

≥ 50 A: 0.2%*RG

Note [1]: (ppm = parts per million) (e.g., 10ppm = 0.001%).

Note [2]: The clamp of 5A model is standard, and other models is option.

• Voltage input: 10 V~480 V, 6-digits decimal display.

• Current input (direct measurement): 0.05 A~12 A, 6-digits display.

• Current input (clamp measurement): 0.1 A~6 A, 6-digits display.

 

2 Frequency/Phase

Frequency

Range

45.000 Hz65.000 Hz

Resolution

0.001 Hz

Accuracy

± 0.01 Hz

Phase

Range

0.000°359.999°

Resolution

0.001°

Accuracy

Direct Measurement: ± 0.05°

Clamp Measurement: ± 0.2°

 

3 Three Phase Power / Energy Measurement

Power/Energy Parameters

Accuracy

Direct Measurement

Clamp Measurement

Class 0.05

Class 0.02

Class 0.05

Class 0.02

Active P/E | cos φ| ≥0.5

± 0.05%*FS[3]

± 0.02%*FS[3]

± 0.2%*FS[3]

± 0.1%*FS[3]

Reactive P/E | sin φ| ≥0.5

± 0.1%*FS[3]

± 0.05%*FS[3]

± 0.5%*FS[3]

± 0.2%*FS[3]

Apparent power

± 0.1%*FS[3]

± 0.05%*FS[3]

± 0.5%*FS[3]

± 0.2%*FS[3]

Power factor

± 0.0005

± 0.0005

± 0.002

± 0.002

Note [3]: FS=voltage range value × current range value.

• Power factor measurement range: -1.000 0... 0.000 0... 1.000 0.

• Standard electric energy pulse output: high frequency full range value corresponds to 60 kHz, low frequency full range value corresponds to 6 Hz.

• Standard electric energy pulse input: frequency ≤ 200 kHz, voltage: 0... 3.3 V... 24 V.