Portable Partial Discharge (PD) Tester MCPD001
Can detect PD activities in bother ultrasonic and TEV mode.
LCD backlit display.
Can test switchgear, overhead cables including transmission line, and etc.
Protection: IP54.
Chargeable batteries power supply.
TEV measuring range 0-60dBmV; Ultrasonic measuring range -7 to 68dB μV.
Technical Parameters
| TEV | |
| Sensor | Capacitive |
| Measuring range | 0 - 60dBmV |
| Resolution | 1dB |
| Accuracy | ± 1dB |
| The number of pulses per cycle maximum | 655 |
| Minimum pulse frequency | 10Hz |
| Ultrasonic | |
| Measuring range | -7 to 68 dB μV |
| Resolution | 1dB |
| Accuracy | ± 1dB |
| The sensor sensitivity | -65dB (0dB = 1volt/ bar RMS SPL) |
| Sensor center frequency | 40 kHz |
| Sensor diameter | 16mm |
| Heterodyne frequency | 38.4kHz |
Main Accessories & Specs
| Parabolic Ultrasonic Focusing Sensor | |
| (Optional for overhead assets include transmission line test) | |
| Measurement of gain | 16dB (compared with the internal sensor, from the target 2.5 meters) |
| Sensor center frequency | 40 kHz |
| Sensor diameter | 16mm |
| Laser power | 5 mW, IIIR |
| Laser spot size | 6mm, 5m in the distance |
| The parabolic reflector outer diameter | 275mm |
| The standard parabolic reflector diameter | 250mm |
| Weight | 0.6 kg |
| Flexible sensor (AA) | |
| Option for probe tight spaces (switchgear overhead cable) | |
| Overhead cable | 40kHz |
| sensivity | ≤40dB(V/uPa) |
| Function checker | |
| Used for verifying the working status of PD detector before measuring switchgear, transmission line and other electrical equipments, etc | |
| Battery charger | |
| Rated voltage | 90 264V - AC |
| Frequency | 47 - 63Hz |
| Charging voltage | 6V DC |
| Charging current | 500 mA |
| Required to fully charge time | 8 hours |
| Test cable & Communication cables and other necessary accessory | |